Rules Supplied with Rule Manager - Intergraph Smart Instrumentation - Help

SmartPlant Instrumentation Rule Manager Help

Language
English
Product
Intergraph Smart Instrumentation
Search by Category
Help
Smart Instrumentation Version
2016 SP1 (11.0.1)

SmartPlant Instrumentation Rule Manager is supplied with a set of rules.  These rules consist of:

Engineering

Rules that can be modified by the user. By default these rules are disabled (except for the KKS Cable Name rule). To activate, the user must clear the Disable Rule check box on the General tab of the Rule Properties dialog box of each required rule.

System

Rules that cannot be altered by the user, and are active within SmartPlant Instrumentation at all times, even if Rule Manager has not been selected in the Domain features of the Domain Definition in the SmartPlant System Administration module, to operate.

These Engineering rules can be found in the Interfaces folder:

Rule: Backup Link Master is not Null for DCS/CENTUM CS 3000.

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Channel - DCS Panel*.

Filter Information:

  • [Operand1] Channel DCS Panel*; [Property] Panel Category; [Operator] =; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Channel DCS Panel*; [Property] Panel Manufacturer; [Operator] =; [Property/Value] CENTUM CS 3000; [Logical Operator] And

  • [Operand1] Channel DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Property/Value] Plant.

Consistency information: [Operand1] Instrument; [Property] Backup Link Master; [Copy] None; [Compare] In; [Operand2] Value; [Property/Value] Y,N;  [Action] Error.

Rule: Backup Link Master is not Null for DCS/Emerson Process

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Channel - DCS Panel*.

Filter Information:

  • [Operand1] Channel DCS Panel*; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Channel DCS Panel*; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Channel DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information: [Operand1] Instrument; [Property] Backup Link Master; [Copy] None; [Compare] In; [Operand2] Value; [Property/Value] Y,N;  [Action] Error.

Rule: Both Control System Tag Descriptions Length must be 12 or less for DCS/CENTUM CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Control System Tag.
Component 2: Control System Tag - Panel.

Filter Information:

  • [Operand1] Control System Tag - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS [Logical Operator] And

  • [Operand1] Control System Tag - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And

  • [Operand1] Control System Tag - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Control System Tag; [Property] Control System Tag Description; [Function] Length; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 12; [Action] Error

  • [Operand1] Control System Tag; [Property] Control System Tag Description 2; [Function] Length; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 12; [Action] Error

Rule: Both Channel Name Equals Channel Sequence and between 1-8 or 16-32 for DCS/CENTUM CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Channel.
Component 2: Channel - Panel.

Filter Information:

  • [Operand1] Channel Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS [Logical Operator] And

  • [Operand1] Channel Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And

  • [Operand1] Channel Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Channel; [Property] Channel; [Copy] None; [Compare] =; [Operand2] Channel; [Property/Value] Channel Sequence; [Action] Error

  • [Operand1] Channel; [Property] Channel Sequence; [Copy] None; [Compare] IN; [Operand2] Value; [Property/Value] 1, 2, 3, 4, 5, 6, 7, 8, 16, 17, 18, 19, 20, 21, 22, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32; [Action] Error

Rule: Control Strategy Document Number must be equal to 1 or more for DCS/CENTUM CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Control System Tag.
Component 2: Control System Tag - Panel.

Filter Information:

  • [Operand1] Control System Tag - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS [Logical Operator] And

  • [Operand1] Control System Tag - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And

  • [Operand1] Control System Tag - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information: [Operand1] Control System Tag; [Property] Control Strategy Document Number; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error

Rule: Controller is Unique for Domain

Rule action: Check data.

Priority: 1(low).

Component 1: Controller.

Consistency information: [Operand1] Controller; [Property] Controller; [Copy] None; [Compare] Unique; [Operand2]Controller; [Property/Value] Controller; [Action] Error

Rule: Controller Name Upper Case and Maximum 16 Chars.

Rule action: Check data.

Priority: 1(low).

Component 1: Controller.

Consistency information:

  • [Operand1] Controller; [Property] Controller; [Function] Upper; [Copy] None; [Compare] =; [Operand2]Controller; [Property/Value] Controller; [Action] Warning

  • [Operand1] Controller; [Property] Controller; [Function] Length; [Copy] None; [Compare] <=; [Operand2]Controller; [Property/Value] 16; [Action] Warning

Rule: Copies Bi-directional Linear Type between Instrument and Control System Type

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Control System Tag - Instrument.

Consistency information: [Operand1] Instrument; [Property] Linearity Type; [Copy] <=>; [Compare] =; [Operand2] Control System Tag; [Property/Value] Linearity Type; [Action] Error

Rule: Copy Instrument Function to Control System Tag Function for Virtual Instrument

Rule action: Check data.

Priority: 1(low).

Component 1: Control System Tag.
Component 2: Control System Tag - Instrument.

Filter Information: [Operand1] Control System Tag - Instrument; [Property] Tag Class; [Operator] =; [Operand2] Value; [Property/Value] Foundation/Profibus PA virtual tag

Consistency information: [Operand1] Control System Tag - Panel; [Property] DCS Function Block Type; [Copy] <=; [Compare] =; [Operand2] Control System Tag - Instrument; [Property/Value] Function; [Action] Error

Rule: Copy Panel Manufacturers to WE Manufacturer and slot bigger than 0 for DCS/CENTUM CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Wiring Equipment.
Component 2: Wiring Equipment- Panel.

Filter Information:

  • [Operand1] Wiring Equipment; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Wiring Equipment; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And

  • [Operand1] Wiring Equipment; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment Manufacture; [Copy] <=; [Compare] =; [Operand2] Wiring Equipment - Panel; [Property/Value] Panel Manufacture; [Action] Error

  • [Operand1] Wiring Equipment; [Copy] None; [Compare] Not Empty; [Action] Error

Rule: DCS Function Block Type for Control System Tag must be 16 or less for DCS/CENTUM CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Control System Tag.
Component 2: Control System Tag- Panel.

Filter Information:

  • [Operand1] Control System Tag - Panel; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Control System Tag - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And

  • [Operand1] Control System Tag- Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Control System Tag; [Property] DCS Function Type; [Function] Length; [Copy] None; [Compare] - <=; [Operand2] Value; [Property/Value] IT; [Action] Error

Rule: Fieldbus Device Panel Address must be 20 for FF Instr/DCS/Emerson Process/Backup Link Master = Y

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.

Filter Information:

  • [Operand1] Instrument; [Property] Tag Class;  [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Instrument; [Property] Backup Link Master; [Operator] =; [Operand2] Value; [Property/Value] Y; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] 20; [Action] Error

Rule: Fieldbus Device Panel Address must be 20 for Fieldbus Instr/DCS/Centum CS 3000/Backup Link Master = Y

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.

Filter Information:

  • [Operand1] Instrument; [Property] Tag Class;  [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And

  • [Operand1] Instrument; [Property] Backup Link Master; [Operator] =; [Operand2] Value; [Property/Value] Y; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] 20; [Action] Error

Rule: Fieldbus Device Panel Address must be between 20 and 35 for Fieldbus Instr/DCS/Centum CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.

Filter Information:

  • [Operand1] Instrument; [Property] Tag Class;  [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 20; [Action] Error

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 35; [Action] Error

Rule: Fieldbus Device Panel Address must be between 20 and 35 for Fieldbus Instrument/DCS/Emerson Process

Rule action: Check data.

Priority: 1(low).

Component 1: Instrument.
Component 2: Instrument - Channel - DCS Panel*.

Filter Information:

  • [Operand1] Instrument; [Property] Tag Class;  [Operator] =; [Operand2] Value; [Property/Value] Foundation Fieldbus; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Instrument - Channel - DCS Panel*; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 20; [Action] Error

  • [Operand1] Instrument; [Property] Fieldbus Device Panel Address; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 35; [Action] Error

Rule: I/O Card Name must start with C then equal to number

Rule action: Check data.

Priority: 1(low).

Component 1: Wiring Equipment.
Component 2: Wiring Equipment - Panel.

Filter Information:

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment Category;  [Operator] =; [Operand2] Value; [Property/Value] I/O Card; [Logical Operator] And

  • [Operand1] Wiring Equipment - Panel; [Property] Plant/Reference Panel;  [Operator] =; [Operand2] Value; [Property/Value] Plant; [Logical Operator] And

  • [Operand1] Wiring Equipment - Panel; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Wiring Equipment - Panel; [Property] Panel Category; [Operator] =; [Operand2] Value; [Property/Value] DCS

Consistency information:

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment; [Start] 1; [Length] 1; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] C; [Action] Error

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment; [Start] 2; [Length] 99; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 01; [Action] Error

Rule: Panel Name must start with FCS then [01-31] then [01-64] for DCS/Centum CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Panel.

Filter Information:

  • [Operand1] Panel; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Panel; [Property] Panel Manufacture; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And

  • [Operand1] Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 1; [Length] 3; [Copy] None; [Compare] =; [Operand2] Value; [Property/Value] FCS; [Action] Error

  • [Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 4; [Length] 1; [Copy] None; [Compare] Not Empty; [Action] Error

  • [Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 4; [Length] 2; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error

  • [Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 4; [Length] 2; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 31; [Action] Error

  • [Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 6; [Length] 1; [Copy] None; [Compare] Not Empty; [Action] Error

  • [Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 6; [Length] 2; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error

  • [Operand1] Panel; [Property] Panel; [Function] Substring; [Start] 6; [Length] 2; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 64; [Action] Error

  • [Operand1] Panel; [Property] Panel; [Function] Length; [Copy] None; [Compare] <=; [Operand2] Value; [Property/Value] 7; [Action] Error

Rule: Rack must be between 1 and 15 for DCS/CENTUM CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Rack.
Component 2: Rack - Panel.

Filter Information:

  • [Operand1] Rack - Panel; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Rack - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And

  • [Operand1] Rack - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Rack; [Property] Rack Name; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error

  • [Operand1] Rack; [Property] Rack Name; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 15; [Action] Error

Rule: Rack must be equal to 1 or more for DCS/Emerson Process

Rule action: Check data.

Priority: 1(low).

Component 1: Rack.
Component 2: Rack - Panel.

Filter Information:

  • [Operand1] Rack - Panel; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Rack - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Rack - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Rack; [Property] Rack Name; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Warning

Rule: Slot must be between 1 and 8 for DCS/CENTUM CS 3000

Rule action: Check data.

Priority: 1(low).

Component 1: Slot.
Component 2: Slot - Panel.

Filter Information:

  • [Operand1] Slot - Panel; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Slot - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] CENTUM CS 3000; [Logical Operator] And

  • [Operand1] Slot - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Slot;[Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error

  • [Operand1] Slot;[Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 8; [Action] Error

Rule: Slot must be between 1 and 8 for DCS/Emerson Process

Rule action: Check data.

Priority: 1(low).

Component 1: Slot.
Component 2: Slot - Panel.

Filter Information:

  • [Operand1] Slot - Panel; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Slot - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Slot - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Slot; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 1; [Action] Error

  • [Operand1] Slot; [Copy] None; [Compare] >=; [Operand2] Value; [Property/Value] 8; [Action] Error

Rule: Disables Manufacture; Model; I/O Type; Module; Controller; Name; Type in wiring for DCS/Centum CS 3000

Rule action: Control graphic interface.

Priority: 1(low).

Component 1: Wiring Equipment.
Component 2: Wiring Equipment - Panel.

Filter Information:

  • [Operand1] Wiring Equipment - Panel; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Wiring Equipment - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And

  • [Operand1] Wiring Equipment - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment Manufacture

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment Model

  • [Operand1] Wiring Equipment; [Property] Instrument I/O Type

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment Module

  • [Operand1] Wiring Equipment;

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment Type

Rule: Disables Sequence Address in Channel for DCS/Centum CS 3000

Rule action: Control graphic interface.

Priority: 1(low).

Component 1: Channel.
Component 2: Channel - Panel.

Filter Information:

  • [Operand1] Channel - Panel; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Channel - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Centum CS 3000; [Logical Operator] And

  • [Operand1] Channel - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Channel; [Property] Channel Sequence

  • [Operand1] Channel; [Property] Address

Rule: Disables Series; Type; Manufacture; I/O Type; Redundant Flag in Wiring Equipment for DCS/Emerson Process

Rule action: Control graphic interface.

Priority: 1(low).

Component 1: Wiring Equipment.
Component 2: Wiring Equipment - Panel.

Filter Information:

  • [Operand1] Wiring Equipment - Panel; [Property] Panel Category;  [Operator] =; [Operand2] Value; [Property/Value] DCS; [Logical Operator] And

  • [Operand1] Wiring Equipment - Panel; [Property] Panel Manufacturer; [Operator] =; [Operand2] Value; [Property/Value] Emerson Process; [Logical Operator] And

  • [Operand1] Wiring Equipment - Panel; [Property] Plant/Reference Panel; [Operator] =; [Operand2] Value; [Property/Value] Plant

Consistency information:

  • [Operand1] Wiring Equipment; [Property] Series

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment Type

  • [Operand1] Wiring Equipment; [Property] Wiring Equipment Manufacture

  • [Operand1] Wiring Equipment; [Property] Instrument I/O Type

  • [Operand1] Wiring Equipment; [Property] Redundant

This System rule can be found in the Wiring > Disable Properties folder:

Rule: Double Width in Telecom Equipment

Rule action: Control graphic interface.

Priority: 1(low).

Component 1: Wiring Equipment.

Filter Information:

  • [Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Amplifier; [Logical Operator] Or

  • [Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Hub; [Logical Operator] Or

  • [Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Intercom [Logical Operator] Or.

  • [Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Miscellaneous Telecom Equipment [Logical Operator] Or.

  • [Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] PA Channel [Logical Operator] Or.

  • [Operand1] Wiring Equipment [Property] Wiring Equipment Category [Operator] =; [Operand 2] Value [Property/Value] Switch [Logical Operator] Or. Consistency information: [Operand1]Wiring Equipment; [Property] Double Width

The following rules can be found in the Wiring > Consistency folder:

Rule: Channel Address Should be Unique per I/O Card

Rule action: Check data.

Priority: 1(low).

Component 1: Channel.

Filter Information:

  • [Operand1] Channel [Property] Address [Operator] Not Empty [Logical Operator] AND

  • [Operand1] Channel [Property] Address [Operator] <> [Operand 2] Value [Property/Value] * .

Consistency information:

  • [Operand1] Channel [Property] Address [Copy] | None [Compare] Unique [Operand 2] Channel [Action] Warning.

Rule: KKS Cable Name

Rule action: Check data.

Priority: 1(low).

Component 1: Cable.

Consistency information:

  • [Operand1] Cable [Property] KKS_Application_Area [Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.

  • [Operand1] Cable [Property] KKS_Cable_Key Sequence [Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.

  • [Operand1] Cable [Property] KKS_Cable_Key Sequence_Suffix [Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.

  • [Operand1] Cable [Property] KKS_Function Key [Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.

  • [Operand1] Cable [Property] Cable Name[Copy] | None; [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiKKSCableNum.CableNumbering [Action] Error.

For the KKS Cable Name rule to function correctly do not remove or modify any of the above parameters. You can add extra lines to the rule whose parameters can be used to define the uniqueness of the KKS cable name.

 

The following rule can be found in the Instrument Index > Consistency folder:

Rule: Trim Instrument Tag Names

Rule action: Check data.

Priority: 1 (low).

Component 1: Instrument.

Consistency information:

  • [Operand1] Instrument [Property] Instrument Name [Copy] | None [Compare] Custom Update [Operand 2] Assembly [Property/Value] spiTrimTagName.TrimName[Action] Error.