Available Space (neg. for can) - CAESAR II - Help

CAESAR II Users Guide

Language
Русский
Product
CAESAR II
Search by Category
Help
CAESAR II Version
12

Specifies the amount of room above or below the pipe where you can install the hanger or can. If the value is negative, then CAESAR II assumes that a can is to be installed. If the value is positive, then CAESAR II assumes that a hanger is to be in installed.

Typical units (depending on your unit system):

  • in

  • mm

  • cm

Hangers or cans are selected for a location only if they can be installed in the space allotted. The precise definition of available space varies with the manufacturer. Drawings and tables for each manufacturer are shown at the end of this section.

This is the available vertical clearance for the hanger or can:

Leave the box blank or set to zero if the Available Space is not an important design criterion.

When the available space is the governing factor in a hanger design, several smaller springs are typically chosen in place of one large spring.