In the Domain Explorer, expand the Panels by Category folder and then the Junction Boxes folder.
-
Right-click 101-JB-DCS-001 and on the shortcut menu, click Actions > Connection.
-
Make sure that in the Terminal strip list, 101-JB-DCS-001, TS-1 is selected.
-
In the Domain Explorer, expand the Cables folder and select C-101-JB-DCS-001/1.
-
Drag cable C-101-JB-DCS-001/1 from the Domain Explorer to the first terminal at the right side of the terminal strip.
When you release the mouse button, the Cable Connection Definition dialog box opens.
-
Make sure the End 1 (JB) option button has been selected (as you are dealing with the junction box end of this cable.)
-
Under Cable set connection details, from the Connection Type list, select 3 in a row as the connection type for set 1 (Pr 1).
-
If prompted to apply to all cable sets, click Yes, or select the 3 in a row connection type for each set in turn.
-
Verify that the Select all cable sets check box is selected.
The dialog box should now appear as shown:
-
The connection type determines the way in which the individual wires in a cable set are connected, and how many terminals to leave unconnected between the wires in adjacent cable sets.
-
For a more comprehensive explanation of connection types, see the Wiring in Smart Instrumentation section of the Smart Instrumentation help.
-
-
Click Connect.
The status bar shows the progress as connections are made. The connections are displayed in the Connection window as shown: