  1. In the Domain Explorer, expand the Panels by Category > Junction Boxes hierarchy and then select junction box 101-JB-DCS-001.

  2. Right-click the selected junction box and then on the shortcut menu, click
    Actions > Connection.

  3. Make sure that terminal strip 101-JB-DCS-001, TS-1 is selected in the Terminal strip list (there is only one terminal strip on the list).

  4. In the Cables folder of Domain Explorer, select cable C-101-LT-201 and drag it to the right side of terminal 6.

  5. On the Cable Connection Definition dialog box, make your selections as follows:

    1. Under Cable end to connect, select End 2.

    2. Select the connection type as 3 in a row and select the cable set in the right data window.

  6. Click Connect to make the connection.

  7. After the cable has been connected, open the Point-to-Point Wiring Diagram for the wire connected to terminal 6+ and view the connection. It should go straight to terminal strip FT-1 of the marshaling rack.

  8. Print out the Point-to-Point Wiring Diagram if needed and then click X to close it.

  9. Click X to close the Connection window.

  10. Now select 101-DCS-001 from the DCS Panels folder in the Domain Explorer.

  11. Right-click the selected panel, then on the shortcut menu, click Actions > I/O Assignment.

  12. On the module toolbar, click Explorer Filter icon 16bit to open the I/O Assignment Filter dialog box.

  13. Select the first three filtering criteria and click OK.

  14. In the I/O Assignment window, select tag 101-LT -201 and drag it to channel 3 in the right side pane.

  15. On the Control System Tag Properties dialog box, type BLI 201 and click OK.

  16. Now close the I/O Assignment window and select marshaling rack 101-MR-DCS-001.

  17. Right-click the selected panel, then on the shortcut menu, click Actions > Connection.

  18. In the Terminal strip list, select 101-MR-DCS-001, TP-1.

    Note that your tag wiring has been propagated from the DCS to the marshaling rack terminals.

  19. Close the Connection window.

  20. Right-click the same marshaling rack again, then on the shortcut menu, click Actions > Cross Wiring.

  21. Click to find matching terminals for automatic cross wiring.

    The software finds matching terminals for automatic cross-wiring. You can view them by scrolling down in the Primary Terminal Strip pane:

  22. Click Cross Wire icon 16bit to perform the automatic cross wiring.

  23. Close the Cross Wiring window.

You have successfully added a new tag to your wiring.