Create DCS Side Terminal Strip DCS SIDE-AO by Duplicating JB SIDE-1 - Intergraph Smart Instrumentation - 13.1 - Training - Intergraph Process, Power & Marine Documentation

Intergraph Smart Instrumentation Tutorial

Language
English
Product
Intergraph Smart Instrumentation
Search by Category
Training
Smart Instrumentation Version
13.1
  1. In the Reference Explorer, expand the hierarchy: Panels > Marshaling Racks > TYPICAL MARSHALING.

  2. Right-click terminal strip JB SIDE-1 and then on the shortcut menu, click Duplicate.

  3. On the Terminal Strip Properties dialog box, change the terminal strip name to DCS SIDE-AO.

  4. Click OK.

    Terminal strip DCS SIDE-AO now appears in the Reference Explorer under marshaling rack TYPICAL MARSHALING.

  5. Expand DCS SIDE-AO as we want to have a 4-channel AO terminal strip.
    You will now delete the surplus terminals in terminal strip DCS SIDE-AO:

  6. In the Reference Explorer, select terminal 5+ and while holding down SHIFT, select Terminal 16SH; this action selects all the terminals between 5+ and 16SH.

    1. On your keyboard, press DELETE.

    2. When prompted, click Yes to confirm the deletion.

      Only 12 terminals (from 1+ to 4SH) now remain in terminal strip DCS SIDE-AO:

The same result can be achieved by creating a new terminal strip configuration using the New > Terminal Strip command on the shortcut menu.

You have now completed the creation of marshaling rack TYPICAL MARSHALING with its internal terminal strip.