Retrieve DeltaV Data - Intergraph Smart Instrumentation - Help

Intergraph Smart Instrumentation Help

Language
English
Product
Intergraph Smart Instrumentation
Search by Category
Help
Smart Instrumentation Version
13.1

Before retrieving data, you must configure Smart Instrumentation to work in file mode. For details, see Configure Smart Instrumentation to Publish and Retrieve Data in File Mode.

  1. In Smart Instrumentation, select Tools > Interfaces > DeltaV.

  2. Under Data transfer mode, select Retrieve DeltaV data and select OK.

  3. In the Select Data XML File window, navigate to the .xml file that contains the DeltaV data and select Open.

    SHARED Tip After selecting the file, two more windows open: Select Meta-data XML File and Select Tombstones XML File. Just select Cancel in both windows.

  4. On successful completion of the retrieval, select Close on the message box that appears, or if errors occurred, select View Log to troubleshoot them.

  5. Select SmartPlant > To Do List.

    If using fieldbus tags, after retrieving the DeltaV data, but before running any tasks from the To Do List, you must make associations between Foundation Fieldbus device types, instrument manufacturers, and Smart Instrumentation instrument types. For more information, see Associate Device Types for DCS Vendors.

  6. In the To Do List window, select all the Create tasks for the DeltaV items; however, do not select the Update task for the CS Tag.

  7. From the To Do List toolbar, select Run TaskPPM All Outputs Graphic.

    • Performing this action creates the DeltaV controllers, slots, I/O cards, and so forth in the Domain Explorer under the Controllers folder.

    • For more details of available options when running tasks, see Run Tasks from the To Do List.

  8. In the Domain Explorer, create a DCS and rack as needed, and then drag a DeltaV slot to the rack.

  9. In the To Do List window, run the Update task for the CS Tag.

See Also

View the Log File for a DCS Vendor