Calculate Tube Flowmeter Parameters - Intergraph Smart Instrumentation - Help

Intergraph Smart Instrumentation Help

Language
English
Product
Intergraph Smart Instrumentation
Search by Category
Help
Smart Instrumentation Version
13.1

This option enables you to calculate tube flowmeter parameters based on the fluid state values of the flowmeter and the values retrieved from the Process Data module. In a calculation data sheet for a flowmeter item, you can accept or modify these values, or enter additional values. Then, in the Flowmeter Calculation dialog, you calculate the tube flowmeter parameters for a selected tube flowmeter, view and print out the calculation results.

  1. Open the Flowmeter Calculation dialog for the tube flowmeter that you want to calculate.

  2. From the Flowmeter type list, select the tube flowmeter type.

  3. From the Sub type list, select the tube flowmeter sub-type, if available.

  4. Type the required values in the fields next to the other two calculation options that you have not selected. Smart Instrumentation will then use these values to calculate the tube flowmeter parameters for the selected option.

  5. In the Tube group box, view the data in the Material field and the corresponding linear expansion coefficient value in the Linear expansion coefficient field.

    • The data in the Material field is retrieved from the Process Data module.

    • The linear expansion coefficient value for the displayed pipe is the standard value taken from the Smart Instrumentation database.

    • From the Linear expansion coefficient list of units of measure, you can select a required unit of measure for the current linear expansion coefficient.

  6. In the Throat group box, select the required throat material.

    • The Material list contains standard options provided with Smart Instrumentation. If the required throat material is not in the list, select from the list the MATERIAL NOT LISTED option and in the Linear expansion coefficient field type the required linear expansion coefficient.

    • If you select a standard option from the Material list, you cannot change the linear expansion coefficient value for the displayed throat material because this is the standard value taken from the Smart Instrumentation database.

    • When calculating the tube flowmeter parameters for the steam fluid state, in the Water in steam, %wt field, type the percentage of water in steam.

    • If the value in the Full scale flow field has been changed, you can select PPM All Outputs Graphic to retrieve the values from the Process Data module.

  7. Under Select calculate field, select one of the following options to calculate the tube flowmeter parameters:

    • Throat diameter

    • Full scale flow

    • Differential range

  8. Select OK to carry out and display the calculation results.

  9. Examine the calculation results and possible calibration error messages.

    • The values of pressure loss in the results comes from the default values for differential range flow set in the Units of Measure and Accuracy dialog.

    • When sizing flowmeters for Liquids and Water, the software checks whether Downstream pressure is greater than Vapor pressure. If it is, the program continues sizing. If it is not, critical flow takes place, and the program advises you to check the input data.

  10. To recalculate the tube flowmeter parameters, enter the new data and then select Calculate.

  11. Select Close to return to the calculation data sheet, where you can select to generate a report for the current calculation result. Error messages also appear in a calculation report.