Parameter |
Description |
---|---|
Commodity |
The commodity representing electricity to determine the utility rate. |
EfficiencyLossAt1 |
Efficiency Loss at 1% Voltage Imbalance (Default is 2%) |
EfficiencyLossAt2 |
Efficiency Loss at 2% Voltage Imbalance (Default is 5%) |
EfficiencyLossAt3 |
Efficiency Loss at 3% Voltage Imbalance (Default is 10%) |
EfficiencyLossAt4 |
Efficiency Loss at 4% Voltage Imbalance (Default is 18%) |
EfficiencyLossAt5 |
Efficiency Loss at 5% Voltage Imbalance (Default is 25%) |
HistoryDays |
Number of past days before the current date/time over which to calculate the average value of the measured Power Factor. |
SampleSize |
Minimum number of measurements required for the calculation. |
DefaultRecipient |
Used if the Performance Manager on the equipment is empty. |
Default Efficiency Loss percentages based on source: Nema-MG1.